Site Kolej Tentera Udara, Alor Setar
Date 15-01-2000
Products HOKKIM HAMF-1 Integrated AMF Control Board
HOKKIM TUV-N Under Voltage Relay
Switchboard Manufacturer Kejuruteraan Letrik Ngai Heng
Problem Gen-set cannot stop when TNB supply returned
Detected Shut Down Timer (SDT) setting at the AMF board during commissioning was set at 10 minutes. The person in-charge complaints too long the setting.
Remarks Adjusted knob at the STD to set it to 3 minutes as requested.
Also help to modified the control circuit for the change-over contactor as the existing unit found to have problem during our visit to the site.Rectified by adding timer to change from gen-set contactor when TNB supply returns.